Detail LXCVR SINGLE PHASE UNDER & OVER VOLTAGE PLUS TIME DELAY MXCVR 230 VAC
BROYCE CONTROL LXCVR SINGLE PHASE UNDER AND OVER VOLTAGE PLUS TIME DELAY MXCVR - 230 VAC
Brand = BROYCE CONTROL
Part Number = LXCVR (NEW Part Number) : MXCVR (OLD Part Number) Same Product 100%
Description = Single Phase Under and Over Voltage Plus Time Delay
Voltage = 230 VAC
Monitoring function = Under/Over voltage
Trip level = Under: 75 – 95%/Over: 105 – 125%
Hysteresis = ≈2%
Time delay = 0.2 – 10s
Output = SPDT 8A @ 250V (AC1)
Dimensions(mm) = W:17.5 x H:89 x D:66.5
LXCVR
Under and Over voltage monitoring (Window)
Monitors own supply
Adjustable Trip levels
Adjustable Time delay
SPDT Relay output
17.5mm wide, DIN Rail mount
UL Listed
When power is applied, the output relay will energise provided the monitored supply voltage is above the set Under voltage trip level and below the set Over voltage trip level.
Under voltage:
If the voltage decreases below the set Under voltage trip level, the relay will de-energise. The voltage must increase above the trip level plus the set hysteresis setting before the relay will re-energise.
Over voltage:
If the voltage increases above the set Over voltage trip level, the relay will de-energise. The voltage must decrease below the trip level minus the set hysteresis setting before the relay will re-energise.
Generator
Tampilkan Lebih Banyak